BC Rapid Transit Company March 11, 2026 OMCI Simulation Room Noise Survey _ - 8 - 2044.20383.2026 7 DISCUSSION AND CONCLUSIONS The purpose of this noise survey was to identify potential noise concerns related to the two server racks located in the training simulation room on Level 2 of OMC1. Three (3) initial spot noise measurements were collected: two (2) within the training simulation room and one (1) in the open office area outside the training simulation room, with the highest readings recorded at 65.7 dBA and a peak of 89.3 dBC. Additionally, continuous data log was collected at the Southeast corner of the room near a training simulation desk, approximately 1 meter from two server racks, from 7:34 AM to 4:12 PM (8 hours and 38 minutes). The projected 10-hour TWA was 57.6 dBA, with a maximum recorded peak of 86.7 dBC. Based on the noise measurements noted above, the measured noise levels are well below the occupational exposure limit of 85 dBA and 140dBC and therefore indicate a low risk of worker overexposure. 8 RECOMMENDATIONS Based on sampling results, site observations and the site history, Arcose recommends the following: 1. The continuous operational noise from the server racks was observed to be low in intensity and is not expected to represent an occupational noise exposure risk based on the noise measures collected. Additional sampling should be considered if the equipment is modified or if additional equipment/racks are installed to meet operational needs. Arcose Consulting Ltd.